Name:Danfoss Thermostatic Expansion Valves Orifice T2-05 068-2008
Place of Origin:China
Brand:Danfoss
Model NO:068-2008
N Series:R22/10.5kw,R407C/11.3kw,R134a/8.6kw,R404A/7.7kw
Allow working pressure:28bar
Domine Cooling capacity:0.5~15.5kW (0.15~4.5TR)
Max test pressure:36bar
Orifice:05
Temp:-40~+10℃/-40~+50℉
For type:T2/TE2
Weight:0.02kg
Refrigerant:R22

Product Description

Danfoss Thermostatic Expansion Valves Orifice T2-05# 068-2008

Product Description

T 2/TE 2 orifice, strainer and label; Orifice assemblies with filters, designed for use with either solder adapter product configurations or standard product configurations.

Product Features

Solder connection

Requires solder adaptor for inlet

The rated capacity is based on:

Evaporating temperature te = +5°C for range N (-40 - 10°C) and te = -30°C for range B (-60 - -20°C)

Condensing temperature tc = +32°C

Refrigerant temperature ahead of valve tl = +28°C



Brand: Danfoss
Colour: -
Connection Size: -
Connection Type: -
Length (M): -
Material Type: -
Model Number: T2 & TE2
Nominal Running Current (A): -
Operating Temperature: -
Pressure: -
Voltage: -
Warranty: 1 Year
Phase: -
Refrigerant Suitability: R134a, R404A, R507, R22, R407C
Valve Connections: -
Defrost: -
Evaporator Fans: -
Cable Length (mtr): -


No.

0X

00

01

02

03

04

05

06

Code No.

068-2002

068-2003

068-2010

068-2015

068-2006

068-2007

068-2008

068-2009



 

 
Orifice model
 
·                                 refrigerating capacity
(TR)
·                                 refrigerating capacity
KW
 
Product code
R22 R407C R134A R404A
R507
R22 R407C R134A R404A
R507
0X 0.15 0.16 0.11 0.11 0.5 0.5 0.4 0.38 068-2002
00 0.3 0.3 0.25 0.21 1.0 1.1 0.9 0.7 068-2003
01 0.7 0.8 0.5 0.45 2.5 2.7 1.8 1.6 068-2010
02 1.0 1.1 0.8 0.6 3.5 3.8 2.6 2.1 068-2015
03 1.5 1.6 1.3 1.2 5.2 5.6 4.6 4.2 068-2006
04 2.3 2.5 1.9 1.7 8.0 8.6 6.7 6.0 068-2007
05
 
3.0 3.2 2.5 2.2 11.3 11.3 8.6 7.7 068-2008
06 4.5 4.9 3.0 2.6 16.7 16.7 10.5 9.1 068-2009

 

Origional orifice for danfoss thermostatic expansion valve

Danfoss Model T2 & TE2 - With Interchangeable Orifice
Assembly
Part
Number
(kW) Orifice
No.
R404A R22 R134a
 -40°to +10°C  -60° to -25°C  -40°to +10°C  -60°to -25°C  -40°to +10°C  -60°to -25°C
Orifice Assembly Nominal Capacity
068-2002 0.38 0.38 0.5 0.5 0.4 0X
068-2003 0.78 0.78 1 0.7 0.9 0
068-2010 1.68 1.68 2.5 1 1.8 1
068-2015 2.18 2.18 3.5 2.1 2.6 2
068-2006 4.28 3.58 5.2 2.8 4.6 3
068-2007 6.08 4.98 8 4.2 6.7 4
068-2008 7.78 6.08 10.5 5.2 8.6 5
068-2009 9.18 6.68 15.5 7 10.5 6