Danfoss Solenoid Valve refrigeration system controls EVR2 032F8056 Flare AC
EVR is a direct or servo-type solenoid valve, using for fluid, suction and heat pipe with fluorinated refrigerants. EVR is available either as a single valve or the like separate components, i.e. valve body, coil and flanges (EVR 15) must be ordered separately.
Features:
1. Can be used for various occasions like cold storage, freezing and air conditioning devices occasions.
2. Provide normally closed style and normally open style.
3. Wide selection of various AC or DC solenoid valve coil.
4. Suitable for all fluorinated refrigerants.
5. Design for medium temperature up to 105℃.
6. MOPD of solenoid valve with 12W coil could be reached 25bar.
7. Flare connection could be reached 5/8 inch.
8. Soldering connection could be reached 2 1/8 inch.
9. Extended nozzle for soldering connection
---let installation more convenient
---no need to dismounting valve body when soldering connection
10. EVR also could provide flanges connection solenoid valve.
Technical data:
Refrigerant: CFC, HCFC, HFC
Medium temperature: 10W or 12W coil: -40~105℃
Defrosting period maximum temperature: 130℃
Model | Cooling capacity(R22)kW | Cooling capacity(R404A)kW | ||||||
-25℃/45℃ | -10℃/45℃ | -25℃/45℃ | -10℃/45℃ | |||||
Minimum cooling capacity | Maximum cooling capacity | Minimum cooling capacity | Maximum cooling capacity | Minimum cooling capacity | Maximum cooling capacity | Minimum cooling capacity | Maximum cooling capacity | |
EVR2 | 0 | 2.8 | 0 | 2.9 | 0 | 1.7 | 0 | 1.8 |
EVR3 | 0 | 4.7 | 0 | 4.8 | 0 | 2.8 | 0 | 3.1 |
EVR6 | 8 | 14 | 8.3 | 14.6 | 4.8 | 8.3 | 5.2 | 9.2 |
EVR10 | 18.8 | 32.5 | 19.6 | 34.4 | 11.3 | 19.8 | 12.3 | 21.5 |
EVR15 | 25.9 | 45.5 | 27 | 47.4 | 15.6 | 26.8 | 17 | 29.5 |
EVR20 | 49.8 | 87.5 | 52 | 91.5 | 30 | 51.5 | 32.7 | 57.5 |
EVR22 | 59.8 | 104.5 | 62.4 | 107.6 | 36 | 62.5 | 39.3 | 68.5 |
EVR25 | 118 | 173.5 | 123 | 182.5 | 71 | 104.5 | 77.5 | 113.5 |
EVR32 | 188 | 275.5 | 197 | 292.5 | 114 | 168.5 | 124 | 182.5 |
EVR40 | 295 | 435.5 | 308 | 456.5 | 178 | 262.5 | 194 | 285.5 |
Model | Required coil type | Connection size | Code No. | |||||
Flare | Solder | |||||||
Imperial Units | Metric | Imperial Units/Metric | Imperial Units | Metric | With manual operation | Without manual operation | ||
EVR2 | AC | 2 | 6 | 032F8056 | 032F1201 | 032F1202 | ||
EVR3 | AC / DC | 2 | 6 | 032F8107 | 032F1206 | 032F1207 | ||
3 | 10 | 032F8116 | 032F1204 | 032F1208 | ||||
EVR6 | 3 | 10 | 032F8072 | 032F1212 | 032F1213 | |||
4 | 12 | 032F8079 | 032F1209 | 032F1236 | ||||
EVR10 | 4 | 12 | 032F8095 | 032F1217 | 032F1218 | |||
5 | 16 | 032F8098 | 032F1214 | 032F1214 | ||||
EVR15 | 5 | 16 | 032F8101 | 032F1228 | 032F1228 | |||
5 | 16 | 032F8100 | 032F1227 | |||||
7 | 22 | 032F1225 | 032F1225 | |||||
EVR20 | AC | 7 | 22 | 032F1240 | 032F1240 | |||
7 | 22 | 032F1254 | ||||||
9 | 28 | 032F1244 | 032F1245 | |||||
DC | 7 | 22 | 032F1264 | 032F1264 | ||||
7 | 22 | 032F1274 | ||||||
EVR22 | AC | 11 | 35 | 032F3267 | 032F1267 | |||
EVR25 | AC/DC | 9 | 032F2200 | 032F2201 | ||||
9 | 28 | 032F2205 |